Cable run length checker
An in-wall access point is fed by one cable from the patch panel to its wall box. Enter that run and the cords at each end to check it against the two length limits in the ANSI/TIA-568 cabling standards. The result is an estimate worked out from the lengths you type; only a cable certifier measures a real link.
What this models. One conventional copper twisted-pair fixed run plus two equipment cords, checked for length only. It makes no allowance for cord gauge, temperature or the application, and some cords can require a shorter channel even at 10 m of cords or less. The result is a length estimate for the layout you describe, not a certification.
Not checked yet
CordsRun in the wall90 m link limit, counted from the start of the run (after the panel cord)100 m channel limit, counted from the start of the panel cord
How the check works
channel = panel cord + run + wall plate cord ≤ 100 m (about 328 ft)
cords = panel cord + wall plate cord; the 90 + 10 model allows 10 m (about 33 ft)
margin = limit − length; 1 ft = 0.3048 m exactly
Limits are compared in metres. Feet are converted and rounded for display only.
Assumptions
- The run is solid-conductor copper cable in the walls from the patch panel to the wall box. When a wall plate cord is used, that run is treated as the 90 m permanent link.
- The 100 m channel is the 90 m link plus up to 10 m of cords. When both length limits are met but the cords total more than 10 m, the result says "outside the simple model" instead of a pass, because longer stranded cords shorten the run that is allowed. Cord de-rating is not modelled, and some cords (see the 28 AWG article below) can need a shorter channel even at 10 m of cords or less.
- If a field-terminated cable plugs straight into the access point, enter 0 for the wall plate cord. That layout is a modular plug terminated link (MPTL) rather than a permanent link plus cord, so the result is a length estimate for that layout, not a statement of how it would be tested; see the EXW explanation below.
- Phones, cameras or computers plugged into the access point's own Ethernet ports are on separate links. Check each of those on its own.
- Length only. Cable category, terminations, bundling and heat can also make a link fail when it is within length.
The limits come from the ANSI/TIA-568 series of cabling standards, the series that includes ANSI/TIA-568.2-D (TIA has announced its successor, 568.2-E). The standards are sold by TIA, so the figures are cited here through the sources below. For power over the same cable, see the PoE+ and PoE++ budget chart.
Sources
- Length measurements for the DSX CableAnalyzer Series Testers, Fluke Networks (90 m and 100 m design limits)
- Top 10 Cable Testing Mistakes to Avoid, Fluke Networks (90 m fixed link, 100 m channel, 10 m of cords in the conventional model)
- The Skinny on 28 AWG Patch Cords, Fluke Networks (why some cords need a shorter channel)
- How Far Can You Run an Ethernet Cable? Maximum Length Explained, trueCABLE
- EXW frequently asked questions, FAQ-009, EXW (modular plug terminated link)
- TIA Publishes New Standards- ANSI/TIA-568.2-E and ANSI/TIA-568.5-1, Telecommunications Industry Association (edition context only; it gives no length limits)
- NIST Guide to the SI, Appendix B: Conversion Factors, National Institute of Standards and Technology (1 ft = 0.3048 m)